Termination – Powerware FCC 15 User Manual

Page 14

Advertising
background image

WIRING THE MODBUS CARD

EATON Powerware

®

Modbus

®

Card User’s Guide

S 164201376 Rev C www.powerware.com

10

3

8

7

9

1

6

2

4

5

Figure 9. RS-485 DB-9 Pin Numbers

Table 2. RS-485 DB-9 Pin Assignments

Pin Number

Modbus Card Signal Name

RS-485 Network Signals

Master Signal Name

1

RxD(+)

TxD(+)

2

TxD(+)

RxD(+)

3

Signal common

Signal common

4

Reserved

5

Reserved

6

RxD(–)

TxD(–)

7

TxD(–)

RxD(–)

8

Reserved

9

Reserved

Termination

C A U T I O N

Termination resistors should be placed only at the extreme ends of the RS-485 network. No
more than two termination points should be used in the RS-485 network.

Termination is not required unless the Modbus Card is located at the
end of the RS-485 network or the length of the network cable is
excessive.

If receive termination is required, an on-board 120 ohm termination
resistor may be selected by setting S2-3 to the ON position. A 120 ohm
resistor will be placed in parallel with the RxD(+) and RxD(–) lines (see
Figure 10).

If transmit termination (four-wire networks) is required, an on-board
120 ohm termination resistor may be selected by setting S2-4 to the ON
position. A 120 ohm resistor will be placed in parallel with the TxD(+)
and TxD(–) lines (see Figure 10).

Advertising