MODBUS CARD CONFIGURATION

EATON Powerware

®

Modbus

®

Card User’s Guide

S 164201376 Rev C www.powerware.com

14

2.

Press [Enter]. The Configuration screen appears (see Figure 13).

Powerware Modbus Card
Version 1.00 (1-16-02)

Current Configuration:

Baud Rate:

9600

Slave Address:

29

-----------------------------------------------------------------------------

Valid Commands:

AD Change Slave Address, usage AD n,

where n is the new slave address for the card (1 - 247 valid).

BD Change Modbus Baud Rate, usage BD n,

where n is the new baud rate (1200, 2400, 4800, 9600, 19200).

SA Save Configuration

-----------------------------------------------------------------------------

Figure 13. Configuration Screen

If the Configuration screen does not appear, press [Enter] one more
time.

If you still do not see the Configuration screen, check the following
conditions:

S

The communication settings of the terminal should be
9600 baud, No parity, 8 data bits, 1 stop bit, and no hardware
handshaking.

S

If the serial configuration is correct, check the cabling to be sure
all connections are secure.

S

Verify that your terminal emulation program is on the correct
communication port for serial communication.

S

Verify that the UPS has input power and is turned on.

3.

To configure the Modbus Card baud rate, type BD followed by a
space and the baud rate (1200, 2400, 4800, 9600, or 19200) and
press [Enter]. The default is 9600 baud. This setting affects both
RS-232 and RS-485 Modbus connections.