INTEGRATING THE UPS

EATON Powerware

®

Modbus

®

Card User’s Guide

S 164201376 Rev C www.powerware.com

21

Table 5. Read Input Registers - Modbus Function Code 04 (Input Registers Start at 30000)

Register

Meter Name

Scale

Unit

1

OUTPUT VOLTS AB

/10

Volts

2

OUTPUT VOLTS BC

/10

Volts

3

OUTPUT VOLTS CA

/10

Volts

4

INPUT VOLTS AB

/10

Volts

5

INPUT VOLTS BC

/10

Volts

6

INPUT VOLTS CA

/10

Volts

10

BYPASS VOLTS AB

/10

Volts

11

BYPASS VOLTS BC

/10

Volts

12

BYPASS VOLTS CA

/10

Volts

19

INPUT CURRENT PHASE A

/10

Amps

20

INPUT CURRENT PHASE B

/10

Amps

21

INPUT CURRENT PHASE C

/10

Amps

22

OUTPUT TRUE POWER

/10

kW

23

INPUT TRUE POWER

/10

kW

24

OUTPUT APPARENT POWER

/10

kVA

25

INPUT APPARENT POWER

/10

kVA

26

OUTPUT POWER FACTOR

/100

27

INPUT POWER FACTOR

/100

28

OUTPUT FREQUENCY

/10

Hz

29

INPUT FREQUENCY

/10

Hz

30

INVERTER FREQUENCY

/10

Hz

31

BYPASS FREQUENCY

/10

Hz

33

BATTERY CURRENT

/10

Amps

34

BATTERY VOLTAGE

/10

Volts

35

% BATTERY LEFT

/10

%

36

BATTERY TIME REMAINING

/10

Minutes

60

INVERTER VOLTS PHASE A

/10

Volts

61

INVERTER VOLTS PHASE B

/10

Volts