INTEGRATING THE UPS

EATON Powerware

®

Modbus

®

Card User’s Guide

S 164201376 Rev C www.powerware.com

20

Unit

Format

Value

Name

Register

162

Building Alarm 2

1

BOOL

Status

163

Building Alarm 1

0

BOOL

Status

169

Output overload

0

BOOL

Status

172

DC link over voltage

0

BOOL

Status

173

DC link under voltage

0

BOOL

Status

174

Rectifier failed

0

BOOL

Status

176

Battery contactor fail

0

BOOL

Status

177

Bypass breaker fail

0

BOOL

Status

191

Battery current limit

0

BOOL

Status

194

Output current over 100%

0

BOOL

Status

199

Shutdown imminent

0

BOOL

Status

200

Battery low

0

Status

212

Battery DC over voltage

0

BOOL

Status

214

Power supply failure

0

BOOL

Status

229

Network not responding

0

BOOL

Status

241

Emergency shutdown command

0

BOOL

Status

249

Bypass not available

0

BOOL

Status

251

Battery contactor open

0

BOOL

Status

252

Inverter contactor open

0

BOOL

Status

270

Battery totally discharged

0

BOOL

Status

295

Battery not charged

0

BOOL

Status

312

UPS On Battery

0

BOOL

Status

313

UPS On Bypass

1

BOOL

Status

314

Load Dumped (Load Power Off)

0

BOOL

Status

337

Fan Failure

0

BOOL

Status

345

Transformer Over Temperature

0

BOOL

Status

361

Input Breaker Failed

0

BOOL

Status