Analog inputs, Analog outputs, Discrete inputs – Hamilton Sundstrand Company ACT2000 User Manual

Page 23: Figure 1-9. typical analog input connection, Figure 1-10. typical analog output connection

Advertising
background image

Analog Inputs

The analog input, DEMAND, has a current range of 4 - 20 mA. It is
electrically isolated up to 500 VAC from the enclosure, 120 VDC power,
digital I/O, and serial interface. The analog interfaces are not isolated from
each other. See Figure 1-9 for a typical analog input connection.

ACT2000

4-20mA INPUT

CONTROLLER 4-20mA OUTPUT

+

-

DEMAND [BRN]

DEMAND RTN [WHT/BRN]

200

Ω

+

-

Figure 1-9. Typical Analog Input Connection

Analog Outputs

The analog outputs, MOTOR CURRENT and POSITION, have a current
range of 4 - 20 mA. They are electrically isolated up to 500 VAC from the
enclosure, 120 VDC power, digital I/O, and serial interface. The analog
interfaces are not isolated from each other. See Figure 1-10 for a typical
analog output connection.

CONTROLLER 4-20mA INPUT

ACT2000 4-20mA OUTPUT

+

-

POSITION

[YEL]

MTR CURRENT

[BLU]

POSITION RTN

[WHT/YEL]

MTR CURRENT RTN [WHT/BLU]

<500

Ω

+

-

Figure 1-10. Typical Analog Output Connection

Discrete Inputs

The discrete inputs are 24 VDC ON (High) and 0 VDC OFF (Low). They
are electrically isolated up to 500 VAC. See Figure 1-11 for a typical
discrete input connection.

CONTROLLER DISCRETE OUTPUT

ACT2000 DISCRETE INPUT

RUN RTN [WHT/VIO]
RESET RTN [WHTGRY]

RUN

[VIO]

RESET

[GRY]

Figure 1-11. Typical Discrete Input Command Connection

INSTALLING THE ACT2000