Installing the redundant –48 vdc power supply, Installing the redundant –48 vdc power supply, Procedure – Paradyne 3161-B3 User Manual

Page 31

Advertising
background image

2. Installation

3160-A2-GB21-90

February 2001

2-7

Installing the Redundant –48 Vdc Power Supply

To install the DSU/CSU using a redundant –48 Vdc SELV power supply, refer to

Figure 2-11, –48 Vdc Redundant Source Power Supply Pinouts

, and use the

following procedure.

Procedure

To install the redundant – 48 Vdc power supply:

1. Connect the black wire to the –48 Vdc return source B.

2. Connect the red wire to the –48 Vdc return source A.

3. Connect the green wire to a suitable ground.

4. Connect the orange wire to the –48 Vdc input source B.

5. Connect the blue wire to the – 48 Vdc input source A.

6. Cut the white wire off at the outer insulation.

7. Plug the power connector into the DSU/CSU.

Figure 2-11. –48 Vdc Redundant Source Power Supply Pinouts

1

2

3

4

5

6

BLACK

RED

GREEN

WHITE

ORANGE

BLUE

– 48 VDC RETURN B

– 48 VDC RETURN A

GROUND

– 48 VDC INPUT B

– 48 VDC INPUT A

99-14300-02

X

DSU/CSU POWER

PLUG

TO CUSTOMER-SUPPLIED BATTERY

Advertising
This manual is related to the following products: