OPERATION

EATON Powerware

®

9125 Two-in-One UPS (2500/3000 VA) User’s Guide

S 164201374 Rev D

www.powerware.com

40

Bypass Mode

In the event of a UPS overload or internal failure, the UPS transfers your
equipment to utility power. Battery mode is not available; however, the
utility power continues to be passively filtered by the UPS. The

indicator illuminates. The UPS transfers to Bypass mode when:

S

The UPS has an overtemperature condition.

S

The UPS has an overload condition of 101 to 150% for 30 seconds.

S

The UPS detects a fault in the battery or UPS electronics.

Standby Mode

When the UPS is turned off and remains connected to utility power, the
UPS is in Standby mode. The

μ

indicator flashes and the bar graph

indicators are off, indicating that power is not available to your
equipment. The battery recharges when necessary.

NOTE For 220–240V models, the output receptacles may remain electrically live (up to
110–120V). Unplug the UPS to ensure power is not available to the output receptacles.