47

Table 3. Communication Port Pin Assignment

Pin Number

Signal Name

Function

Direction from the UPS

1

Low Batt

Low Battery relay contact; 20 mA, 30 Vdc contact rating

Out

2

TxD

Transmit to external device

Out

3

RxD

Receive from external device

In

4

DTR

PnP (Plug and Play) from external device (tied to Pin 6)

In

5

GND

Signal common (tied to chassis)

6

DSR

To external device (tied to Pin 4)

Out

7

RTS

PnP from external device (default) or On Bypass relay
contact (jumper-selectable)

In / Out

8

AC Fail

AC Fail relay contact; 20 mA, 30 Vdc contact rating

Out

9

Power Source

+V (8 to 24 volts DC power)

Out

The On-Bypass Relay Contact. You can enable the On-Bypass relay using
the jumper on the Single-Port Card. The jumper default is disabled.

To enable the On-Bypass relay:

1.

Remove the Single-Port Card on the UPS rear panel. Retain the
screws (see Figure 36).

Figure 36. Removing the Single-Port Card

2.

Move the J3 jumper to the AS/400

®

position to enable the

On-Bypass relay, as shown in Figure 37.