The Simplified Installation (Return/Return Method)

Defrost air port needs to be drawn from clean
area without combustion appliances. To avoid
backdrafting of combustion products, never
draw defrost air from a room with a naturally
aspirated appliance, i.e. furnace, hot water
heater, gas dryer, stove, fire place etc.

WARNING

Air

Handler

Outdoors

*Unit is normally balanced on
HIGH speed with air handler
blower ON.

Cool Air

Return

Return Air

Fresh Air From Outside

3' (1 m) min.

recommended

Stale Air To Outside

Stale Air From Building

Fresh Air To House

High efficiency filter
or electronic air cleaner

Field-supplied
Balancing Damper
(optional)

FIVE PORT MODELS - Simplified Installation for Models RNC10/RNC20

Weatherhood arrangement - requires a minimum
of 6' (2m) separation and a minimum of 18" (460mm)
clearance above grade or anticipated snow level.

CAUTION

It is mandatory that the furnace run continuously or HRV

operation be interlocked with the furnace.

Check local codes/authority having jurisdiction for

acceptance.

HRV must be balanced.

Refer to “Airflow Balancing” in this manual.

WARNING

RETURN AIR

DIRECT CONNECTION of both the HRV SUPPLY AIR STREAM and

EXHAUST AIR STREAM to the FURNACE COLD AIR RETURN

Outdoors

Cool Air

Return

NOTES:

1. Furnace blower is required to operate when ventilation from HRV is required.

The furnace must be set to run continuously or interlocked with HRV.

2. A minimum separation of 40 inches (1 m) is required between the two direct connections.
3. The exhaust air connection should be upstream of the supply air connection to prevent

exhausting any fresh air.

4. Weatherhood arrangement is for drawing purposes only. Six feet (2 m) minimum separation

required. Eighteen inches (460 mm) above grade minimum.

5. Due to the differences in pressure between the HRV and the equipment it is being

connected to, the HRV's airflow must be confirmed on site, using the balancing
procedure found in the installation manual.

3' (1 m) min.

recommended

Forced Air

Furnace

40" (1m) MINIMUM

FOUR PORT MODELS

40" (1m) MINIMUM

*Unit is normally balanced on
HIGH speed with air handler
blower ON.