Performance, Dimensions rnc200, Engineering data - hrv model rnc200 – Lifebreath RNC120D User Manual

Page 6

Advertising
background image

6

THERMALLY CONDUCTIVE, PATENTED ALUMINUM CORE
The cross-flow heat recovery core transfers heat between the two air streams.
It is easily removed for cleaning or service.
MOTORS AND BLOWERS
Each air stream has one centrifugal blower driven by a common PSC motor. 2 speed fan operation.
FILTERS
Washable air filters in exhaust and supply air streams.
MOUNTING THE HRV
Four threaded inserts at corners of case designed to accept four reinforced
polyester straps that are supplied with the unit.
DEFROST
Recirculating damper defrost system.
CASE
Twenty gauge prepainted galvanized steel (G60) for superior corrosion resistance. Insulated to prevent
exterior condensation. Drain connections two - 1/2" (12mm) OD.
WEIGHT 71 lbs. (32.5 kg)

SHIPPING WEIGHT 73 lbs. (33.5 kg)

CONTROLS - HRV System Control
HRV defaults to LOW SPEED when plugged in. HIGH SPEED option is accessible by connecting remote
controls to designated terminals inside electrical box of HRV.

Standard LOW SPEED SETTING can be increased to medium low.
Off (Standby)/Low or OFF/HIGH speed operation is also available.

OPTIONAL MAIN CONTROLS (only one main control can be installed on the system)
99-116

Dehumidistat Ventilation Control - Dehumidistat Dial, ON/OFF Switch and LOW/HIGH

Switch (3 wire) 20 gauge wire (min.) 100' length (max.)

99-2040

20/40 ON/OFF Dehumidistat - Dehumidistat Dial, ON/OFF Switch and 20/40 Switch.

The 20/40 Switch will toggle from continuous low speed ventilation to intermittent low
speed ventilation of 20 minutes fan ON and 40 minutes fan OFF. (4 wire) 20 gauge wire
(min.) 100' length (max.)

99-RECIRC

Recirculation Control - Dehumidistat Dial, ON/OFF Switch and Recirculation Switch.

The Recirculation Switch will toggle from continuous low speed ventilation to continuous
low speed recirculation. (4 wire) 20 gauge wire (min.) 100' length (max.)

99-130

Remote Dehumidistat - Dehumidistat Dial only. (2 wire) 20 gauge wire (min.) 100' length

(max.)

OPTIONAL TIMERS
99-132

20 Minute Fan Timer - initiates high speed ventilation for 20 minutes. (3 wire) 20 gauge

wire (min.) 100’ length

99-104

Digital Electronic Timer- initiates high speed ventilation for 20, 40 or 60 minutes, (3
wire) 20 gauge wire (min.) 100' length

99-101

60 Minute Crank Timer - initiates high speed ventilation for up to 60 minutes, (2 wire)
20 gauge wire (min.) 100' length (max.)

WARRANTY
Units carry a lifetime warranty on the heat recovery core and a 5 year replacement parts warranty.

BALANCING DAMPER

STALE AIR

FROM INSIDE

FRESH AIR

FROM OUTSIDE

STALE AIR

TO OUTSIDE

FRESH AIR

TO INSIDE

14 3/4"

(375 mm)

19"

(483

mm)

*All Duct
Connections
6" (150 mm)

CONDENSATE DRAINS

FILTERS

BLOWERS

*NOTE: Front
clearance
of 25 inches
(635 mm)
is recommended
for ser vicing unit.

RECIRCULATING

DEFROST

DAMPER

MOTOR

CORE

33 5/8"

(850 mm)

Dimensions
RNC200

inches (mm)

Performance

(HVI certified)

Net supply air flow in cfm (L/s) against external static pressure

E.S.P

(external static pressure)

[cfm (L/s)]

@ 0.1" (25 Pa)

207 (97)

@ 0.2" (50 Pa)

200 (94)

@ 0.3" (75 Pa)

184 (87)

@ 0.4" (100 Pa)

171 (80)

@ 0.5" (125 Pa)

152 (71)

@ 0.6" (150 Pa)

130 (61)

@ 0.7" (175 Pa)

116 (55)

@ 0.8" (200 Pa)

86 (40)

Max. Temperature Recovery

74%

Sensible Effectiveness
@ 66 cfm (31 L/s)

32°F (0°C)

74%

*Sensible Efficiency
@ 66 cfm (31 L/s)

32°F (0°C)

64%

*Sensible Efficiency
@ 109 cfm (51 L/s)

-13°F (-25°C)

62%

VAC @ 60HZ

120

WATTS / Low speed.

87

WATTS / High speed

164

Amp rating

1.4

*Sensible Efficiency – thermal **Latent Efficiency – moisture
Note: Effectiveness - based on temp. differential between the 2 airstreams
Efficiency – takes into account all power inputs

1

2

3

40

60

80

100

120

140

160

180

200

220

0

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

Static Pressure (in w.g.)

A

ir

Fl

ow

(

c

fm

)

3 - High Speed
*2 - Medium Low Speed
*1 - Low speed

* Manufacturers Data

Engineering Data - HRV

Model RNC200

Date: _______________________________________________

Tag: __________________________Qty:__________________

Project: _____________________________________________

Engineer:____________________________________________

Contractor: __________________________________________

Supplier: ____________________________________________

Quote#: _____________________________________________

Submitted by: ________________________________________

All units conform to CSA and UL standards

SP-RNC200