Fresh air, Stale air, Airflow reference chart – Lifebreath RNC120D User Manual

Page 27

Advertising
background image

27

Air Flow Balancing using the Door Ports

Models RNC155 and RNC200 Only

The door ports ( MODELS RNC155 & RNC 200) are designed
to quickly and measure the airflows for balancing.

Normally the HRV would be balanced on high speed. If the
HRV is connected to a forced air system, both systems should be
set to run at the highest operational speed when balancing is
performed.

Balancing Procedure
Step 1

Remove balancing port covers.

Step 2

Insert one end of each connection hose into a rubber
fitting. (Use light pressure until fitting is snug).

Step 3

Attach the connection hoses to pressure gauge

Step 4

Fresh Air - Connect hoses to door ports as illustrated
(record reading).

Step 5

Stale Air - Connect hoses to door ports as illustrated
(record reading).

Step 6

Refer to the Airflow Reference Chart for the conversion
of gauge reading to airflow reading.

Step 7

Damper the airflows as required to balance the system.
The fresh airflow must equal the stale airflow.

Step 8

Repeat steps 4 to 7 as required to confirm airflows.

Magnehelic Door Port Balancing Kit

Part No. 99-206

Use the Magnehelic Gauge Kit (Part No. 99-206) for door port
balancing.

1 - Pressure Gauge

4 - Rubber Fittings

2 - Connection Hoses

1 - Instruction Page

Fresh Air

Step 4

Measuring Fresh Air Side (Connect to both ports at the same time).

MAGNEHELIC

Pressure
Gauge

MAGNEHELIC

Pressure
Gauge

Stale Air

Step 5

Measuring Stale Air Side (Connect to both ports at the same time).

Pressure Gauge

Reading

Fresh Air

Stream Flow

Stale Air

Stream Flow

(in w.g.)

(cfm)

(cfm)

0.070

75

54

0.080

80

59

0.090

84

65

0.100

89

70

0.110

93

75

0.120

98

81

0.130

102

86

0.140

106

91

0.150

111

97

0.160

115

102

0.170

120

114

0.180

124

118

0.190

128

123

0.200

133

128

0.210

137

133

0.220

142

138

0.230

146

143

0.240

151

148

0.250

155

153

0.260

159

158

0.270

164

163

0.280

168

167

0.290

173

172

0.300

177

177

0.310

181

182

0.320

186

187

0.330

190

192

0.340

195

197

Airflow Reference Chart

Door port balancing is only available for Models
RNC155 and RNC200.