Performance, Engineering data - hrv model rnc20, Dimensions rnc20 – Lifebreath RNC120D User Manual

Page 8

Advertising
background image

8

All units conform to CSA and UL standards

Engineering Data - HRV

Model RNC20

Date: _______________________________________________

Tag: __________________________Qty:__________________

Project: _____________________________________________

Engineer:____________________________________________

Contractor: __________________________________________

Supplier: ____________________________________________

Quote#: _____________________________________________

Submitted by: ________________________________________

SP-RNC20

THERMALLY CONDUCTIVE, PATENTED ALUMINUM CORE
The cross-flow heat recovery core transfers heat between the two air streams.
It is easily removed for cleaning or service.
MOTORS AND BLOWERS
Each air stream has one centrifugal blower driven by a common PSC motor. 2 speed fan operation.
FILTERS
Washable air filters in exhaust and supply air streams.
MOUNTING THE HRV
Four threaded inserts at corners of case designed to accept four PVC reinforced
polyester straps that are supplied with the unit.
DEFROST
Damper defrost system; defrosts automatically as the outdoor temperature falls.
CASE
Twenty gauge prepainted galvanized steel (G60) for superior corrosion resistance. Insulated to prevent
exterior condensation. Drain connections two - 1/2" (12mm) OD.
WEIGHT 63 lbs. (28.7 kg) SHIPPING WEIGHT 67 lbs. (30.4 kg)

CONTROLS - HRV System Control
HRV defaults to LOW SPEED when plugged in. HIGH SPEED option is accessible by connecting remote
controls to designated terminals inside electrical box of HRV.

Standard LOW SPEED SETTING can be increased to medium low.
Off (Standby)/Low or OFF/HIGH speed operation is also available.

OPTIONAL MAIN CONTROLS (only one main control can be installed on the system)
99-116

Dehumidistat Ventilation Control - Dehumidistat Dial, ON/OFF Switch and LOW/HIGH

Switch (3 wire) 20 gauge wire (min.) 100' length (max.)

99-RECIRC

Recirculation Control - Dehumidistat Dial, ON/OFF Switch and Recirculation Switch.

The Recirculation Switch will toggle from continuous low speed ventilation to continuous
low speed recirculation. (4 wire) 20 gauge wire (min.) 100' length (max.)

99-130

Remote Dehumidistat - Dehumidistat Dial only. (2 wire) 20 gauge wire (min.) 100' length

(max.)

OPTIONAL TIMERS
99-132

20 Minute Fan Timer - initiates high speed ventilation for 20 minutes. (3 wire) 20 gauge

wire (min.) 100’ length

99-104

Digital Electronic Timer- initiates high speed ventilation for 20, 40 or 60 minutes, (3
wire) 20 gauge wire (min.) 100' length

99-101

60 Minute Crank Timer - initiates high speed ventilation for up to 60 minutes, (2 wire)
20 gauge wire (min.) 100' length (max.)

WARRANTY
Units carry a lifetime warranty on the heat recovery core and a 5 year replacement parts warranty.

33-5/8"

STALE AIR

TO OUTSIDE

FRESH AIR

FROM OUTSIDE

STALE AIR

FROM INSIDE

FRESH AIR

TO INSIDE

CONDENSATE DRAINS

BLOWERS

DEFROST

DAMPER

DEFROST

PORT

*

All Duct

Connections
6"(150mm)

FILTERS

*NOTE:

Front clearance of

25 inches (635 mm)

is recommended

for ser vicing unit.

19"

(483)

14 3/4"

(375)

BALANCING DAMPER

Dimensions
RNC20

inches (mm)

*Sensible Efficiency - thermal **Latent Efficiency - moisture

Note: Effectiveness - based on temp. differential between the 2 airstreams
Efficiency - takes into account all power inputs

Performance

(HVI certified)

Net supply air flow in cfm (L/s) against external static pressure

E.S.P

(external static pressure)

[cfm (L/s)]

@ 0.1" (25 Pa)

214 (101)

@ 0.2" (50 Pa)

206 (97)

@ 0.3" (75 Pa)

193 (91)

@ 0.4" (100 Pa)

184 (87)

@ 0.5" (125 Pa)

170 (80)

@ 0.6" (150 Pa)

155 (73)

@ 0.7" (175 Pa)

137 (65)

Max. Temperature Recovery

69%

Sensible Effectiveness
@ 119 cfm (56 L/s)

32°F (0°C)

67%

*Sensible Efficiency
@ 119 cfm (56 L/s)

32°F (0°C)

60%

*Sensible Efficiency
@ 117 cfm (55 L/s)

-13°F (-25°C)

60%

VAC @ 60HZ

120

WATTS / Low speed.

70

WATTS / High speed

182

Amp rating

1.4

1

2

3

20

40

60

80

100

120

140

160

180

200

220

240

0

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

Static Pressure (in w.g.)

A

ir

Flow (

c

fm

)

3 - High Speed
*2 - Medium Low Speed
*1 - Low speed

*Manufacturer’s data

Advertising
This manual is related to the following products: