SECTION 13: T

ROUBLESHOOTING

31

SECTION 13: TROUBLESHOOTING
13.1 General

Ensure air flow through the

heat exchanger is

appropriate per the rating

plate.

If problems persist, contact

Roberts-Gordon, LLC at

www.rg-inc.com

Heater Operating

TROUBLESHOOT ENDS.

No

Replace limit switch.

The limit switch has

tripped. See Manual Reset

Limit Switch Figure.

No

Use Troubleshooting for

Automatic Ignition Burner

Systems section to test burner.

Has burner “Locked Out”?

Yes

No

With external controls (i.e.

thermostat) on, does the

burner continue through the

heating cycle?

No

Yes

Does the flue blower run?

No

Use Troubleshooting for

Flue Blower section to test

fan.

Yes

Yes

Burner has locked out due

to ignition failure. Use

Troubleshooting for Automatic

Ignition Burner Systems

section to test burner.

Is ignition control showing a

"2 flashes" LED code?

Yes

No

Yes

Fan and limit switch are

operating normally.

Replace temperature limit

switch.

UHD 75: Press in reset

button on manual reset limit

switch. UHD 100 - 125: Wait

10 - 15 minutes for limit

switch to cool. Does fan

stop running?

No

Is ignition control showing a

"4 flashes" LED code?

Yes

No

Yes

Turn on supplies.

Are gas & electrical

supplies on?

No

Yes

START

WARNING

Explosion Hazard

Installation, service and annual inspection
must be done by a contractor qualified in
the installation and service of gas-fired
heating equipment or your gas supplier.

Turn off gas and electrical supplies before
performing service or maintenance.

Failure to follow these instructions can
result in death, injury or property damage.