Roberts Gorden Combat UHD[X][S][R] 75 User Manual

Page 42

Advertising
background image

UHD L

OW

P

ROFILE

D

UCT

F

URNACE

I

NSTALLATION

O

PERATION

AND

S

ERVICE

M

ANUAL

36

14.2 Burner Compartment

14.2.1 Burner Injectors

Remove flexible
air duct from spigot

Viewing port
for flame probe

Flame Probe

Burner
Compartment
Cover

Ignition Electrode

Remove screws and
pull off burner cover

NOTE: Separated combustion
model

shown.

The burner compartment is a sealed
compartment. Following any work,
re-seal the compartment with the
gas pipe rubber seal fully in place
and all screws fitted and tight.

MODEL

UHD[X][S][R] 75

UHD[X][S][R] 100

UHD[X][S][R] 125

Orifice Quantity

5

6

7

Natural Gas (G20)

Orifice Marking

49

46

46

P/N

91930049

91930046

91930046

Propane (G31)

Orifice Marking

1.15 mm

1.25 mm

1.25 mm

P/N

91930115

91930125

91930125

Remove manifold

screws and pull

out manifold

Manifold

Inshot

Burners

Orifices

Manifold

Mounting

Bracket

Grommet

Unscrew

Orifices

Manifold

Marking

Folded

Hem

Ensure gas tight fitting
of injectors.

Ensure correct alignment
with burners.

Ensure all pipe joints are
gas tight.

Advertising