SECTION 15: S

PECIFICATIONS

41

15.2 General Technical Data Table

*Do not exceed the maximum length of flue stated or heater may not operate properly.

15.3 Technical Data Table

Model

UHD[X][S][R]

75

UHD[X][S][R]

100

UHD[X][S][R]

125

Full Load Amps @ 115 V

A

1

2

2

Minimum Air Volume

CFM

850

950

1020

Temperature Rise @ Minimum Air Volume

°F (°C)

68 (20)

78 (26)

92 (33)

Heat Exchanger Pressure Drop @ Minimum Air Volume

in wc

0.06

0.05

0.06

Maximum Air Volume

CFM

2650

3660

4750

Temperature Rise @ Maximum Air Volume

°F (°C)

22 (-6)

22 (-6)

20 (-7)

Heat Exchanger Pressure Drop @ Maximum Air Volume

in wc

0.36

0.55

0.98

Flue Size/Air Intake**

in (cm)

4 (10)-All models

Model

UHD[X][S][R]

75

UHD[X][S][R]

100

UHD[X][S][R] 125

Total Input

(Btu/h) x (1000)

75

100

125

Total Output

(Btu/h) x (1000)

61.5

82

102.5

Efficiency

%

82-All models

Natural Gas (G20) Data - Inlet Pressure 5.0 in wc Min., 14 in wc Max.

Burner Pressure

in. wc

3.5

2.6

3.3

LPG / Propane (G31) Data - Inlet Pressure 12.0 in wc Min., 14 in wc Max.

Burner Pressure

in. wc

10.0

9.1

10.0