Installing the storage tank, Typical installation – Rheem Marathon Thermal MTS105200 User Manual

Page 8

Advertising
background image

8

Installing  the  storage  tank.

Typical  Installation

Temperature & Pressure

Relief Valve

Union

(The addition of a union at

this point will help in the

replacement of the T &

P Relief Valve should the

need arise.)

Drain Pipe

Drain Valve

Support the relief valve drain pipe

using metal strapping or wire

fastened to the structure overhead

Seal Ring

(Inside nut)

Hex Union Nut

(Relief Valve)

No threads permitted

on end of Drain Pipe.

6” Maximum distance from

drain pipe to suitable open

drain.

Cold Inlet Shut Off

Thermal Expansion

Tank (if required)

See thermal

expansion section

on page 5.

Heat Trap 6"

Minimum

Pre-solder 12" minimum

stub pipes before installing

to unit.

Hot Water Outlet

Bottom Water Connection Port

Top Water Connection Port