5.4 Type Test Specifications

Electrical Safety

Levels

Comments

Dielectric Withstand

2 kV rms for 1 minute

ANSI/IEEE C37.90 (1989)

IEC 60255-5 (Section 6)

High Voltage Impulse

5 kV peak

IEC 60255-5 (Section 8)

Insulation Resistance

500 VDC for 1 minute

IEC 60255-5 (Section 6

Table 13: Type Test Specification - Electrical Safety

Electrical Environment

Levels

Comments

High Frequency Disturbance

(Oscillatory)

2.5 kV @ 1MHz for 2s

ANSI/IEEE C37.90.1

IEC 60255-22-1

IEC Surge

4 kV / 2 kV

IEC 61000-4-5

(Level 4)

IEC Fast Transient

2 kV / 1 kV

IEC 61000-4-4

(Level 4)

ANSI/IEEE Fast Transient

4 kV

ANSI/IEEE C37.90.1

IEC Radiated RFI Immunity

10 V/m

IEC 61000-4-3

ANSI/IEEE Radiated RFI

Immunity

35 V/m

ANSI/IEEE C37.90.2

ESD

(Electrostatic Discharge)

15 kV (air discharge)

8 kV (contact)

IEC 61000-4-2

(Level 4)

Table 14: Type Test Specification - Electrical Environment

Atmospheric Environment

Levels

Comments

Temperature (Dry Cold)

-40

°C

IEC 60068-2-1

Test Ad: 16 hrs @ -40

°C

Temperature (Dry Heat)

85

°C

IEC 60068-2-2

Test Bd: 16 hrs @ 85

°C

Humidity

95%

non-condensing

IEC 60068-2-30

Test Db: 6 cycles, 55

°C, 95% Humidity

Table 15: Type Test Specification - Atmospheric Environment