Technical specifications, Power supply specifications, Critical alarm relay specifications – RuggedCom RUGGEDBACKBONE RX1510 User Manual

Page 39: 1 power supply specifications, 2 critical alarm relay specifications

Advertising
background image

RuggedBackbone™ RX1510

Installation Guide

Chapter 4

Technical Specifications

Power Supply Specifications

33

Technical Specifications

Section 4.1

Power Supply Specifications

Table 15: Power Supply Specifications

Input Range

Power

Supply Type

Min

Max

Internal

Fuse Rating

Max. Power

Consumption

a

Max Power

Output

Connections

88 VDC

300 VDC

HI

85 VAC

264 VAC

2A(T)

b

65W Max

50W

Screw

terminal block

88 VDC

300 VDC

HIP

85 VAC

264 VAC

2A(T)

b

65W Max

50W

Pluggable

terminal block

24

10 VDC

36 VDC

2A(T)

b

52W Max

42W

Screw

terminal block

24P

10 VDC

36 VDC

2A(T)

b

52W Max

42W

Pluggable

terminal block

48

36 VDC

72 VDC

2A(T)

b

52W Max

42W

Screw

terminal block

48P

36 VDC

72 VDC

2A(T)

b

52W Max

42W

Pluggable

terminal block

a

Power consumption varies based on configuration.

b

(T) denotes time-delay fuse.

Section 4.2

Critical Alarm Relay Specifications

Table 16: Form C Contact Relay Specifications

Voltage

Current

30VDC

5A

250VAC

6.25A

Advertising