Emi and environmental type tests – RuggedCom RUGGEDBACKBONE RX1510 User Manual

Page 45

Advertising
background image

RuggedBackbone™ RX1510

Installation Guide

Chapter 5

EMI And Environmental Type Tests

39

EMI And Environmental Type

Tests

Table 25: IEC 61850-3 EMI Type Tests

Test

Description

Test Levels

Severity

Levels

Enclosure Contact

+/- 8 kV

4

IEC 61000-4-2

ESD

Enclosure Air

+/- 15 kV

4

IEC 61000-4-3

Radiated RFI

Enclosure Ports

20 V/m

Note

a

Signal ports

+/- 4kV @ 2.5kHz

Note

a

D.C. Power ports

+/- 4kV

4

A.C. Power ports

+/- 4kV

4

IEC 61000-4-4

Burst (Fast Transient)

Earth ground ports

+/- 4kV

4

Signal ports

+/- 4kV line-to-earth,

+/- 2kV line-to-line

4

D.C. Power ports

+/- 2kV line-to-earth,

+/- 1kV line-to-line

3

IEC 61000-4-5

Surge

A.C. Power ports

+/- 4kV line-to-earth,

+/- 2kV line-to-line

4

Signal ports

10V

3

D.C Power ports

10V

3

A.C. Power ports

10V

3

IEC 61000-4-6

Induced (Conducted) RFI

Earth ground ports

10V

3

40 A/m, continuous,

1000 A/m for 1 s

Note

a

IEC 61000-4-8

Magnetic Field

Enclosure Ports

1000 A/m for 1 s

5

D.C. Power ports

30% for 0.1s, 60% for

0.1s, 100% for 0.05s

N/A

IEC 61000-4-29

Voltage Dips & Interrupts

A.C. Power ports

30% for 1 period, 60% for 50 periods

N/A

IEC 61000-4-11

Voltage Dips & Interrupts

A.C. Power ports

100% for 5 periods,

100% for 50 periods

N/A

Signal ports

2.5kV common, 1kV

diff. mode@1MHz

3

IEC 61000-4-12

Damped Oscillatory

D.C. Power ports

2.5kV common, 1kV

diff. mode@1MHz

3

Advertising