4. MINIMUM CLEARANCES FROM VENT/AIR INLET TERMINATION

U.S. Installations1

Canadian Installations2

A

Clearance above grade, veranda,
porch, deck, or balcony

1 ft (30 cm)

1 ft (30 cm)

B

Clearance to window or door that may

4 ft (1.2m) below or to side of

be opened

opening; 1 foot (30 cm) above

3 ft (91 cm)

opening

C

Clearance to permanently closed window

*

*

D

Vertical clearance to ventilated soffit located above

5 ft (1.5m)

*

the terminal within a horizontal distance of 2 ft (61cm)
from the centerline of the terminal

E

Clearance to unventilated soffit

*

*

F

Clearance to outside corner

*

*

G

Clearance to inside corner

6 ft (1.83m)

*

H

Clearance to each side of center line

*

3 ft (91 cm) within a height

extended above meter/regulator assembly

15 ft above the meter/ regulator

assembly

I

Clearance to service regulator vent outlet

*

6 ft (1.83m)

J

Clearance to non-mechanical air supply inlet to

4 ft (1.2m) below or to

3 ft (91 cm)

building or the combustion air inlet to any other

side of opening; 1 ft

appliance

(30 cm) above opening

K

Clearance to mechanical air supply inlet

3 ft (91 cm) above if within

6 ft (1.83m)

10 ft (3m) horizontally

L

Clearance above paved sidewalk or paved driveway

7 ft (2.13m)

7 ft (2.13m) t

located on public property

M

Clearance under veranda, porch, deck or balcony

*

12 in. (30 cm) TT

1 In accordance with the current ANSI Z223.1/NFPA 54 National Fuel Gas Code
2 In accordance with the current CAN/CGA-B149 Installation Codes
t Vent terminal shall not terminate directly above sidewalk or paved driveway located between 2 single family dwellings that serves both dwellings
TT Permitted only if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the floor and top of terminal and underside
of veranda, porch, deck or balcony is greater than 1 ft (30cm)
* Clearances in accordance with local installation codes and the requirements of the gas supplier

Fig. 20

V = vent terminal X = air supply inlet \\\ = area where terminal is not permitted

Tab. 6