Low voltage high voltage – Raypak XPAK 85 User Manual

Page 36

Advertising
background image

36

REMOTE CONTROL EXTERNAL

SENSOR

0T+

M4

-t°

M2

TANK

THERMOSTAT

V

ROOM

THERMOSTAT

(jumper when

not used)

TANK

SENSOR

-t°

M4a

M3b

M3a

M3

UNDERFLOOR HEATING LIMIT

THERMOSTAT OR

CONDENSATE PUMP ALARM

(jumper when not used)

LOW VOLTAGE

HIGH VOLTAGE

120V

N

L

F=

fuse 4AF

PCB fuse=4AT

Cod. 20003227

3W

BLUE (COMMON)

BR

O

WN (CLOSED)

BLA

CK(OPEN)

Fig. 35

11. TERMINAL STRIP DETAILS

Terminal

Description

Technical

Indications

strip

specifications

reference

M3

Main supply

120 VAC – 60 Hz

The main supply cable must be anchored to the

boiler frame (Fig. 39) and pass through the
strains relief (field supplied). Cable as specified in
the electrical supply.

M3a

3-way valve:
Connections for DHW

Model: Honeywell VC6011 (actuator) + VCZMK6000

external 3-way valve

120 VAC – 60 Hz

(Cartridge valve)
The 3-way valve cable must be anchored to the boiler
frame (Fig. 39) and pass through the strains relief (field
supplied) (Fig. 39). Cable as specified in the electrical
supply.

M4

Outdoor sensor

12 K Ohm B3760

M4

Remote control

Open therm plus protocol

Only Raypak Part No. 013073

M4a

Room thermostat

24 VDC

Volt free (Jumper when not used)

M4a

Tank sensor

10 K Ohm B3435

Immersion type.

for DHW

If the boiler is installed with a tank sensor, the Jumper
on the PCB must be in position 2 (Fig. 61)

M2a

Tank thermostat

On/off (NO)

Volt free

for DHW

If the boiler is installed with a tank termostat, the
Jumper on the PCB must be in position 3 (Fig. 61)

M3b

Under-floor heating limit

On/off (NC)

Volt free.

thermostat and condensate

This is a generic input to lock out the boiler. Jumper when
(generic available alarm) not used). If the contact will be
open the alarm number 21
will appear on the display and the boiler is lock out

High voltage (Fig. 35)

Low voltage (Fig. 35)

Tab. 9

Advertising