Voyageur grand wood insert, F. 2-10-3 rule – Radware VOYAGEUR GRAND WOOD INSERT VOYA-GRAND-MBK User Manual

Page 28

Advertising
background image

Page 28

7075-166C

May 23, 2013

R

VOYAGEUR GRAND Wood Insert

10 ft. (305cm) or more

3 ft. (91cm) Minimum

Less than 10 ft. (305cm)

2 ft. (61cm) Minimum

3 ft. (91cm) Minimum

Wall or Parapet

Flat Roof

3 ft. (91cm)

Minimum

Less than 10 ft. (305cm)

2 ft. (61cm)

3 ft. (91cm)

Minimum

10 ft. (305cm) To Nearest Roofline

2 ft. (61cm)

Pitched Roof

These are safety requirements and are not meant to assure proper flue draft.

Figure 28.1

F. 2-10-3 Rule

Figure 28.2

This appliance is made with a 6 inch (152mm) diameter chimney connector as the flue collar on the unit.

• Changing the diameter of the chimney can affect draft and cause poor performance.
• It is not recommended to use offsets and elbows at altitudes above 4000 feet above sea level and or when

there are other factors that affect flue draft.