7075-166C

May 23, 2013

R

VOYAGEUR GRAND Wood Insert

F. Prefabricated Metal Chimney

E. Metal Heat Circulating Masonry

The chimney can be new or existing, masonry or prefabricated

and must meet the following minimum requirements:
• Must be minimum 6 inch (152mm) inside diameter of

high temperature chimney listed to UL 103 HT (2100

o

F)

or ULC S628.

• Must use components required by the manufacturer for

installation.

• Must maintain clearances required by the manufacturer

for installation.

• Refer to manufacturers instructions for installation

•This insert is listed to UL 1482 Standard and is

approved for installation into listed factory-built solid

fuel fireplaces listed to UL 127 conforming to the follow-

ing specifications and instructions:

•The original factory-built clearance fireplace chimney

cap must be re-installed after installing the approved

chimney liner meeting type UL 103 HT requirements

(2100°F) per UL 1777.

•The liner must be securely attached to the insert flue

collar and the chimney top.

•The air flow of the factory-built solid fuel fireplace

system must not be altered. The flue liner top support

attachment must not reduce the air flow for the existing

air-cooled chimney system.

•No dilution air is allowed to enter the chimney.

1.

Secure the fireplace damper in the open position.

If this cannot be accomplished, it will be necessary

to remove the damper.

2. Seal damper area of chimney around chimney

connector with a high temperature sealant or seal

insert against the face of the fireplace.

3. Both methods must be removable and replaceable

for cleaning and re-installation.

This insert conforms with the safety standard UL-1482 and

ULC S628 (Canada) in all respects and is approved to UL &

ULC safety standards for installation and use within a fire-

place with masonry chimney, in accordance with NFPA 211,

and CAN/CSA-B365-01.

Minimum Width of Cavity Opening - Front

32-7/8*

835

Minimum Width of Cavity Opening - Rear

24*

610

Minimum Height

24*

610

Minimum Depth from Front to Rear

18*

457

Inches

Millimeters

Fire Risk.
When lining air-cooled factory-built chimneys:.
• Run chimney liner approved to UL 1777 Type

HT requirements (2100 degrees F)

• Re-install original factory built chimney cap

ONLY

• DO NOT block cooling air openings in chimney
• Blocking cooling air will overheat the chimney

WARNING

NOTICE: In Canada when using a factory-built chimney it must

be safety listed,

Type UL103 HT (2100oF) [1149oC] CLASS

“A” or conforming to CAN/ULC-S629M, STANDARD FOR

650

o

C FACTORY-BUILT CHIMNEYS.

NOTE: Refer to chimney liner manufacturer for recom-

mendations on supporting the liner. Installation into

fireplaces without a permit will void the listing.

WARNING! Risk of Fire!

Follow venting manufacturer’s clearances and

instructions when installing venting system.

To maintain the functionality of the fireplace’s chimney

system you may use a Simpson Dura-Vent DuraLiner

Slip Hanger, Part # 4671, and attach to the bottom of the

fireplace chimney cap to support the liner. You have two

options to completing the installation.

Option one - Not required to use liner cap:

Re-attach the existing top of the chimney cap.

Option two - Using liner cap:

Re-attach the existing top of the chimney cap and install a

new storm collar and a new liner cap.

*You will need to add additional clearances to these

dimensions for your specific installation. Also allow suf-

ficient clearance if you are installing an outside air kit.