CONNECTIONS – ELECTRICAL


The power supply to the water heater must not be switched on until the water heater is filled
with water.

MEGGER READING
It is not mandatory to conduct a megger test on a plug in appliance, however if a megger test is
conducted on this water heater, then the following should be noted.

Warning: This water heater contains electronic equipment and 500 V insulation tests must only be

conducted between either active and earth or neutral and earth. An active to neutral test WILL damage
the electronics.

An insulation test result of approximately 660 KΩ for this water heater is normal.

Typically the insulation resistance between live and earthed parts of an electrical installation should not
be less than 1 MΩ. However AS/NZS 3000:2000 clause 6.3.3.3.2 ‘Results’ states:

“The value of 1 MΩ may be reduced to:

• 0.01

MΩ for sheathed heating elements or appliances; or

• a value permitted in the Standard applicable to electrical equipment.”

This model water heater is categorised as a ‘stationary class 1 motor operated appliance’ and has been
tested to AS/NZS 3350.1:2002 clause 16 ‘Leakage current and electric strength’ and has passed the
requirements of this Standard. Therefore, this model water heater complies with the condition stated in
AS/NZS 3000:2000 clause 6.3.3.3.2 (b).

ELECTRICAL CONNECTION
All electrical work and permanent wiring must be carried out by a qualified person and in accordance
with the Wiring Rules AS/NZS 3000 and local authority requirements.

Warning: Temperature controllers must not be fitted to this water heater as part of a solar water

heater system because water at a temperature much higher than the controller setting can be delivered.

The water heater requires a 240 V AC, 50 Hz mains power supply for operation. The solar storage tank,
supplied with a 1.8 metre power cord to operate the solar control unit and gas booster, requires a
switched general purpose outlet (GPO) to be located within 1.2 metres of the installation. The GPO
must have a continuous power supply. The GPO is required to be weatherproof if installed outdoors.

The power consumption of the water heater is:

Component

Power

consumption

Comments

Solar controller

3 Watts

Constant load

Solar pump

165 Watts

Maximum load at solar heating cycle start up
(for approximately two (2) minutes)

50 Watts

Average load during the solar heating cycle

Gas booster

150 Watts

Anti frost device active


The water heater will only operate on a sine wave at 50 Hz. Devices generating a square wave cannot
be used to supply power to the water heater.