COMMISSIONING

43

16. Determine the correct amount of water to be added to or closed circuit fluid to be drained from the

heat exchanger if the dynamic level is either below the text marking “MINIMUM FLUID LEVEL
WITH PUMP OPERATING” or more than 150 mm above this mark.

Each 100 mm of fluid level height is equivalent to three (3) litres of closed circuit fluid.

20 mm

0.6 litres

80 mm

2.4 litres

140 mm

4.2 litres

40 mm

1.2 litres

100 mm

3.0 litres

160 mm

4.8 litres

60 mm

1.8 litres

120 mm

3.6 litres

180 mm

5.4 litres

ƒ

Mark the required closed circuit fluid level to be obtained on the side of the solar storage tank
with a non permanent marker beside the clear hose, in relation to the static level marked on the
side of the solar storage tank during step 7.

Eg: If the dynamic level is 30 mm below the text marking, then place a mark 30 mm above the
static level marked on the side of the solar storage tank in step 7. It would be necessary to add
one litre of water to the heat exchanger.

Eg: If the dynamic level is 180 mm above the text marking, then place a mark at least 30 mm,
but no more than 180 mm, below the static level marked on the side of the solar storage tank.
It would be necessary to drain between one litre and five litres of closed circuit fluid from the
heat exchanger.

















If the dynamic fluid level is greater than
150 mm above the text marking, then
place a mark below the static level marked
on the tank of between equal to this
distance and this distance plus 150 mm.

Y mm’

greater

than

150 mm

above text

marking

If the dynamic fluid level is below the text
marking, then place a mark equal to this distance
above the static level marked on the tank

X mm’

below text

marking

static level marked on tank during step 7

mark

X mm’

above

static mark

mark static level to achieve

mark between

Y mm’ and

‘Y + 150 mm’

below static

mark

mark static level to achieve

MINIMUM FLUID LEVEL WITH PUMP OPERATING