5. EMI And Environmental Type Tests

RuggedCom® RuggedSwitch®

33

RSG2300 Installation Guide Rev 110

5. EMI And Environmental Type Tests

Test

Description

Test Levels

Severity

Levels

Enclosure Contact

+/- 8 kV

4

IEC 61000-4-2

ESD

Enclosure Air

+/- 15 kV

4

IEC 61000-4-3

Radiated RFI

Enclosure Ports

20 V/m

X

Signal ports

+/- 4kV @ 2.5kHz

X

D.C. Power ports

+/- 4kV

4

A.C. Power ports

+/- 4kV

4

IEC 61000-4-4

Burst (Fast Transient)

Earth ground ports

a

+/- 4kV

4

Signal ports

+/- 4kV line-to-earth,

+/- 2kV line-to-line

4

D.C. Power ports

+/- 2kV line-to-earth,

+/- 1kV line-to-line

3

IEC 61000-4-5

Surge

A.C. Power ports

+/- 4kV line-to-earth,

+/- 2kV line-to-line

4

Signal ports

10V

3

D.C Power ports

10V

3

A.C. Power ports

10V

3

IEC 61000-4-6

Induced (Conducted) RFI

Earth ground ports

a

10V

3

IEC 61000-4-8

Magnetic Field

Enclosure Ports

40 A/m, continuous,

1000 A/m for 1 s

N/A

D.C. Power ports

30% for 0.1s, 60% for

0.1s, 100% for 0.05s

N/A

IEC 61000-4-29

Voltage Dips & Interrupts

A.C. Power ports

30% for 1 period,

60% for 50 periods

N/A

IEC 61000-4-11

Voltage Dips & Interrupts

A.C. Power ports

100% for 5 periods,

100% for 50 periods

N/A

Signal ports

2.5kV common, 1kV

diff. mode@1MHz

3

D.C. Power ports

2.5kV common, 1kV

diff. mode@1MHz

3

IEC 61000-4-12

Damped Oscillatory

A.C. Power ports

2.5kV common, 1kV

diff. mode@1MHz

3

Signal ports

30V Continuous, 300V for 1s

4

IEC 61000-4-16

Mains Frequency Voltage

D.C. Power ports

30V Continuous, 300V for 1s

4

IEC 61000-4-17

Ripple on D.C.

Power Supply

D.C. Power ports

10%

3

Signal ports

2kVAC (Fail-Safe Relay output)

N/A

D.C. Power ports

1.5kVDC

N/A

IEC 60255-5

Dielectric Strength

A.C. Power ports

2kVAC

N/A

Signal ports

5kV (Fail-Safe Relay output)

N/A

D.C. Power ports

5kV

N/A

IEC 60255-5

H.V. Impulse

A.C. Power ports

5kV

N/A

a

Only applicable to functional earth connections separated from the safety earth connection.

Table 5.1. IEC 61850-3 EMI Type Tests