SECTION 12: S

ERVICING

27

Gas Line and Shut-off
Valves

Check for gas leaks.

See Page 16, Section 8.

Burner Observation
Window

Make sure it is clean and free of cracks or holes.

Clean and replace as required.

Flue Blower Scroll, Wheel
and Motor

Compressed air or a vacuum cleaner may be used to clean dust and dirt.

Inshot Burners and
Orifices

Clear obstructions (even spider webs will cause problems).

Carefully remove any dust and debris from the burner.

Direct-Spark Igniter

Replace if there are cracked ceramics, excessive carbon residue, or erosion
of the electrode.

The electrode gap should be 1/8" (3.2 mm).

Thermostat

There should be no exposed wire or damage to the device or wiring.

See Page 17, Section 9.

Suspension Points

Make sure the heater is hanging securely.

Look for signs of wear on the suspension materials or ceiling.

See Page 8, Figure 3.

Silicone Tubing

Ensure tight, secure fit on all pressure fittings at pressure switch,
burner partition, and blower outlet.

Gas Valve

Verify that cap covering pressure regulator adjustment screw is secure and
has not been tampered with.

Verify all wiring connections.

Condensate Drain
(when installed)

Flush drain and clear any obstructions.

Ductwork

Consult an indoor air quality professional for proper cleaning procedures

Air Circulation Blower

For a complete inspection, refer the manufacturers Installation, Operation and
Service manual.

Wall Tag

If wall tag is present, make sure it is legible and accurate. Please contact
Roberts-Gordon LLC or your ROBERTS-GORDON

®

independent distributor if

you need a wall tag. See Page 2, Section 2.1.