SECTION 14: R

EPLACEMENT

P

ARTS

33

14.2 Burner Compartment

14.2.1 Burner Injectors

MODEL

UHD[X][S][R]

150

UHD[X][S][R]

175

UHD[X][S][R]

200

UHD[X][S][R]

225

UHD[X][S][R]

250

UHD[X][S][R]

300

UHD[X][S][R]

350

UHD[X][S][R]

400

Orifice

Quantity

7

8

9

10

11

12

14

14

Natural Gas (G20)

Orifice

Marking

43

43

2.25 mm

2.25 mm

2.25 mm

40

40

40

P/N

91930043

91930043

91930225

91930225

91930225

91930040

91930040

91930040

Propane (G31)

Orifice

Marking

1.35 mm

1.35 mm

54

54

54

1.45 mm

53

53

P/N

91930135

91930135

91930054

91930054

91930054

91930145

91930053

91930053

Remove flexible

air duct from spigot

Remove

access plate

Remove screws and

pull off burner

compartment cover

Viewing port

for flame probe

Viewing port

for ignition electrode

Flame Probe

Burner

Compartment

Cover

Rubber Seal

Ignition Electrode

The burner compartment is
a sealed compartment.
Following any work,
re-seal the compartment
with the gas pipe rubber
seal fully in place and all
screws fitted and tight.

NOTE: Separated combustion
model shown.

Remove manifold

screws and pull

out manifold

Manifold

Inshot

Burners

Injectors

Burner

Screws

Burner
venturi

Unscrew

Orfices

Manifold

Marking

Folded

Hem

Ensure gas tight fitting of injectors.
Ensure correct alignment with burners.
Ensure all pipe joints are gas tight.

Advertising