13.2 Troubleshooting For Automatic Ignition Burner Systems

If problems persist, contact

Roberts-Gordon LLC at

www.rg-inc.com

Heater Operating

TROUBLESHOOT ENDS.

No

Trace fault in supervision

system. See

Troubleshooting

for Flame Supervision

System section.

Yes

Is ignition control showing

a "2 flashes" LED code?

No

Is the flame current at

least 1 μAmp DC when

the flame ignites?

Ignition control faulty;

replace.

See Ignition Control section.

Is ignition lead okay and

connected?

Is spark electrode okay?

Yes

Replace valve.

Is the gas valve operating?

To test valve, See

Troubleshooting for Gas

Valves section.

No

Does the flame light?

No

Yes

Wait 30 - 40 seconds.

Does ignition spark

operate?

No

Yes

Flue blower faulty;

replace

Burner control faulty or wiring

connections faulty. Repair

or replace as required

Check for too much vent/air inlet duct. Check for blockage in
vent and combustion air circuit. Check for faulty air pressure
switch. Check pressure switch hoses for leaks or cracks.
Do not attempt to circumvent pressure switch circuit to
place unit in operation.See Pressure Switch section for details.

Does air pressure switch

change over?

No

Yes

Is 120 V supply at fan

connections?

Does flue blower run?

No

Yes

Yes

No

Yes

Fan and limit switch are

operating normally.

Replace temperature limit

switch.

Wait 10 - 15 minutes for

limit switch to cool. Does

fan stop running?

No

Is ignition control showing a

"4 flashes" LED code?

Yes

No

Yes

Turn on controls.

Are external controls

(i.e. Thermostat) on?

No

Yes

Turn on supplies.

Are gas & electrical

supplies on?

Yes

START

No

For optimum heater performance, use only replacement parts sold and supplied by Roberts-Gordon.

Conduct start-up procedure as shown on Page 21, Section 10.