SECTION 13: T

ROUBLESHOOTING

31

13.4 Troubleshooting for Gas Valves

13.5 Troubleshooting for Flue Blower

Valve faulty.

Replace with one of

correct type.

Fault elsewhere.

Correct pressure problem.

If problems persist, contact

Roberts-Gordon LLC at

www.rg-inc.com

Valve Operating

TROUBLESHOOT ENDS.

No

Yes

Valve or ignition control

faulty. Replace with
one of correct type.

Does gas pressure at

outlet of valve return to zero or

lower when valve turns off?

No

Yes

Does gas pressure at outlet

of the valve rise when

valve turns on?

No

Yes

Is gas pressure at inlet of the

valve correct for gas type?

Note pressure found.

No

Yes

START

For optimum heater performance, use only replacement parts sold and supplied by Roberts-Gordon.

Conduct start-up procedure as shown on Page 21, Section 10.

If problems persist, contact

Roberts-Gordon LLC at

www.rg-inc.com

Blower Operating

TROUBLESHOOT ENDS.

No

Blower motor faulty.

Replace with correct type.

Check blower motor leads

for loose connections.

Correct power

supply problem.

Yes

START

Does

blower

turn on and

off while burner is firing

continuously?

No

Yes

Does flue blower run

automatically when there

is a call for heat?

No