38

15.2 General Technical Data Table

* Do not exceed the maximum length of flue stated or heater may not operate properly.

15.3 Technical Data Table

Model

UHD

[X][S][R]

150

UHD

[X][S][R]

175

UHD

[X][S][R]

200

UHD

[X][S][R]

225

UHD

[X][S][R]

250

UHD

[X][S][R]

300

UHD

[X][S][R]

350

UHD

[X][S][R]

400

Full Load Amps @ 115 V

A

2

2

2

2

2

2

6

6

Minimum Air Volume

CFM

1360

1400

2050

2100

2350

2700

3120

3420

Temperature Rise @
Minimum Air Volume

°F

(°C)

83

(28)

95

(35)

73

(23)

80

(27)

80

(27)

86

(30)

86

(30)

86

(30)

Heat Exchanger Pressure
Drop @ Minimum Air Volume

in wc

0.02

0.03

0.025

0.035

0.05

0.02

0.03

0.04

Maximum Air Volume

CFM

5800

6850

7750

8300

8850

10200

13600

14200

Temperature Rise @
Maximum Air Volume

°F

(°C)

20

(7)

20

(7)

20

(7)

20

(7)

22

(6)

23

(5)

22

(6)

22

(6)

Heat Exchanger Pressure
Drop @Maximum Air Volume

in wc

0.16

0.29

0.163

0.253

0.35

0.27

0.48

0.53

Flue Size*

in

(cm)

4 - All Models
(10)

Air Intake*

in

(cm)

4

(10)

4

(10)

4

(10)

4

(10)

4

(10)

5

(13)

5

(13)

5

(13)

Model

UHD

[X][S][R]

150

UHD

[X][S][R]

175

UHD

[X][S][R]

200

UHD

[X][S][R]

225

UHD

[X][S][R]

250

UHD

[X][S][R]

300

UHD

[X][S][R]]

350

UHD

[X][S][R]

400

Total Input

(Btu/h) x (1000)

150

175

200

225

250

300

350

385

Total Output

(Btu/h) x (1000)

123

143.5

164

184.5

205

246

287

315.7

Efficiency

%

82 - All Models

Natural Gas (G20) Data - Inlet Pressure 5.0 in wc Min., 14 in wc Max.

Burner Pressure

in wc

3.2

3.4

3.7

3.7

4.0

2.7

2.7

3.3

LPG / Propane (G31) Data - Inlet Pressure 12.0 in wc Min., 14 in wc Max.

Burner Pressure

in wc

9.9

10.4

10.5

10.7

10.5

9.4

9.3

11.1