Jumper setting, A/d calibration, Umper – Omega 1002 User Manual

Page 14: Etting, Alibration, 2 jumper setting, 3 a/d calibration

Advertising
background image

2.2 Jumper Setting

There is only one jumper on the OME-PCI-1002. JP1 is used to select

the analog input type. For single-ended inputs, users should connected pin 1, 3
and pin 2, 4. For differential inputs, Pin 3, 5 and Pin 4, 6 should be connected.

JP1

JP1

1

2

2

1


5

6

6

5

Differential

Inputs

Single-ended

Inputs (Default)







2.3 A/D Calibration



• A/D Calibration for OME-PCI-1002 card
Step 1: Apply +10V to channel 0.
Step 2: Apply +0V to channel 1.
Step 3: Apply -10V to channel 2.
Step 4: Run DEMO6.EXE.
Step 5: Adjust VR1 until channel 0 = fff or ffe
Step 6: Adjust VR2 until channel 1 = 800 or 801
Step 7: Adjust VR3 until channel 2 = 000 or 001
Step 8: Repeat Step 4 & Step 5 & Step 6 until all read

properly.

VR1, VR2, VR3