Troubleshooting, General faults and alarms, En-21 – Omron Healthcare VARISPEEDF7 User Manual

Page 22

Advertising
background image

EN-21

Troubleshooting

‹

General Faults and Alarms

Faults and Alarms indicate unsusal inverter / application conditions.

An alarm does not necessarily switch off the inverter but a message is displayed on the keypad (i.e.
a flashing alarm code) and an alarm output can be generated at the multi-function outputs (H2-01
and H2-02) if programmed. An alarm automatically disappears if the alarm condition is not present
anymore.

A fault switches the inverter output off immediately, a message is displayed on the keypad and the
fault output is switched. The fault must be reset manually after the cause and the RUN signal have
been removed.

The following table shows a list of faults and alarms with their corrective actions.

Display

Alarm

Fault

Meaning

Corrective Actions

BUS

Option Com Err



Option Card Communication Alarm
After initial communication was established, the
connection was lost.

Check the connections and all user-side soft-
ware configurations.

CF

Out of Control



Control Fault
A torque limit was reached continuously for 3
seconds or longer during a deceleration stop in
Open Loop Vector control

Check the motor parameters

CPF00

COM-

ERR(OP&INV)



Digital Operator Communication Fault 1/2
• Communication fault between Operator and

Inverter

• CPU External RAM Fault

• Disconnect the Digital Operator and then

connect it again.

• Cycle the Inverter power supply.
• Replace the Inverter.

CPF01

COM-

ERR(OP&INV)

CPF02

BB Circuit Err



CPF02 Fault
Baseblock circuit error

• Perform an initialization to factory defaults.
• Cycle the Inverter power supply.
• Replace the Inverter.

CPF03

EEPROM Error



CPF03
EEPROM error

CPF04

INternal A/D Err



CPF04
CPU Internal A/D Converter Fault

DEV

Speed Deviation



F1-04 = 0, 1 or 2 and A1-02 = 1 or 3
The speed deviation has been greater than the
setting in F1-10 for a time longer than the setting
F1-11.

• Reduce the load.
• Lengthen the acceleration and deceleration

time

• Check the mechanical system
• Check the settings of F1-10 and F1-11
• Check the sequence and if the brake is

opened when the inverter starts to increase
the speed.



F1-04 = 3 and A1-02 = 1 or 3
The speed deviation has been greater than the
setting in F1-10 for a time longer than the setting
F1-11.

EF

External Fault



Forward/Reverse Run Commands Input
Together
Both the forward and the reverse run commands
are input simultaneously for 500ms or more.
This alarm stops the motor.

Check external sequence logic, so that only
one input is activated at a time.

EF0

Opt External Flt



External fault input from Communications
Option Card

• Check for an external fault condition.
• Verify the parameters.
• Verify communication signals

EFx

Ext Fault Sx





External fault at terminal Sx (x stands for termi-
nals S3 to S7)

Eliminate the cause of the external fault con-
dition.

Ext Run Active

Cannot Reset



Detected after a fault when a RESET command
is input while the RUN command is still active

Remove the RUN signal first and reset the
error.

GF

Ground Fault



Ground Fault
The ground current at the Inverter output
exceeded 50% of the Inverter rated output cur-
rent and L8-09=1 (Enabled).

• Remove the motor and run the Inverter

without the motor.

• Check the motor for a phase to ground

short.

• Check the output current with a clampmeter

to verify the DCCT reading.

• Check the control sequence for wrong

motor contactor signals.

Advertising