The Inverter’s output current exceeded the over-
current detection level.

• Remove the motor and run the Inverter

without the motor.

• Check the motor for a phase-to-phase

short.

• Verify the accel/decel times (C1-

††

).

• Check the Inverter for a phase-to-phase

short at the output.

OH

Heatsnk Overtemp



Heatsink Overheat
L8-03 = 0,1 or 2 and the temperature of the
Inverter's cooling fin exceeded the L8-02 value.

• Check for dirt build-up on the fans or heat-

sink.

• Reduce the ambient temperature around

the drive.

• Replace the cooling fan(s).

Inverter's Cooling Fan Stopped



L8-03 = 3 or 4 and the temperature of the
Inverter's cooling fin exceeded the L8-02 value.

OH1

Heatsink Max Temp



Heatsink Overheat
The temperature of the Inverter’s heatsink
exceeded 105 °C.

• Check for dirt build-up on the fans or heat-

sink.

• Reduce the ambient temperature around

the drive.

• Replace the cooling fan(s).

Inverter’s Cooling Fan Stopped

OL1

Motor Overload



Motor Overload
Detected when L1-01 is set to 1,2 or 3 and the
Inverter’s I²t value exceeded the motor overload
curve.
The overload curve is adjustable using parame-
ter
E2-01 (Motor Rated Current), L1-01 (Motor Pro-
tection Selection) and L2-02 (Motor Protection
Time Constant)

• Recheck the cycle time and the size of the

load as well as the accel/decel times (C1-

††

).

• Check the V/f characteristics (E1-

††

).

• Check the setting of Motor Rated Current

Setting (E2-01).

OL2

Inv Overload



Inverter Overload
The Inverter output current exceeded the Invert-
ers’s overload capability

• Recheck the cycle time and the size of the

load as well as the accel/decel times (C1-

††

).

• Check the V/f Characteristics (E1-

††

).

• Check if the inverter rated current matches

the motor rated current.

OS

Overspeed Det.



F1-03 = 0, 1 or 2 and A1-02 = 1 or 3
The motor speed feedback (U1-05) exceeded
the setting in F1-08 for a time longer than the
setting of
F1-09

• Adjust the ASR settings in the C5 parame-

ter groupt

• Check the reference circuit and reference

gain.

• Check the settings in F1-08 and F1-09



F1-03 = 3 and A1-02 = 1 or 3
The motor speed feedback (U1-05) exceeded
the setting in F1-08 for a time longer than the
setting of
F1-09

OV

DC Bus Overvolt



(only in

stop

condi-

tio)



The DC bus voltage has exceeded the overvolt-
age detection level.
Default detection levels are:
200 V class: 410 VDC
400 V class: 820 VDC

• Increase the deceleration time (C1-02/04)

or connect a braking option.

• Check the power supply and decrease the

voltage to meet the inverter’s specifica-
tions.

• Check the braking chopper / resistor.

PF

Input Phase Loss



Input Phase Loss
Too big DC bus voltage ripple.
Only detected when L8-05=1 (enabled)

• Tighten the input terminal screws
• Check the power supply voltage

PGO

PG Open



PG Disconnection
Detected when F1-02 = 0, 1 or 2 and A1-02 = 1
or 3.
Detected when no PG (encoder) pulses have
been received for a time longer than the setting
in F1-14.

• Fix the broken/disconnected wiring.
• Supply power to the PG properly.
• Check the sequence and if the brake is

opened when the inverter starts to increase
the speed.



PG Disconnection
Detected when F1-02 = 3 and A1-02 = 1 or 3.
PG (encoder) pulses have not been received for
a time longer than the setting in F1-14.

Display

Alarm

Fault

Meaning

Corrective Actions