Operator programming errors, En-23 – Omron Healthcare VARISPEEDF7 User Manual

Page 24

Advertising
background image

EN-23

‹

Operator Programming Errors

An Operator Programming Error (OPE) occurs when two or more parameter related to each other
are set inappropriately or an individual parameter setting is incorrect. The Inverter does not operate
until the parameter setting is corrected; however, no other alarm or fault output will occur. If an OPE
occurs, change the related parameter by checking the cause shown in the table below. When an
OPE error is displayed, press the ENTER key to see U1-34 (OPE Detected). This monitor displays
the parameter that is causing the OPE error.

PUF

DC Bus Fuse Open



DC Bus Fuse Open
The fuse in the main circuit is blown.
Warning:
PG (encoder) pulses have not been received for
a time longer than the setting in F1-14.

• Check the motor and the motor cables for

short circuits or insulation failures (phase-
to-phase).

• Replace the inverter after correcting the

fault.

RR

DynBrk Transistr



Dynamic Braking Transistor
The built-in dynamic braking transistor failed

• Cycle power to the inverter.
• Replace the inverter.

UV1

DC Bus Undervolt



(only in

stop

condi-

tio)



The DC bus voltage is below the Undervoltage
Detection Level
(L2-05). The default settings are:
200V class: 190 VDC
400 V class: 380 VDC

• Check the input voltage.
• Check the wiring of the input terminals.
• Check the input voltage and the wiring of

the input terminals.

• Extend the settings in C1-01/03

Main Circuit MC Operation Failure
No MC response during Inverter operation.

Replace the Inverter.

UV2

CTL PS Undervolt



Control Power Supply Undervoltage
Undervoltage of the control circuit while the
Inverter was running.

• Remove all connection to the control termi-

nals and cycle the power to the Inverter.

• Replace the Inverter.

Display

Meaning

Corrective Actions

OPE01

kVA Selection

Inverter kVA Setting Error

Enter the correct kVA setting in o2-04.

OPE02

Limit

Parameter setting is out of its range

Verify the parameter settings.

OPE03

Terminal

One of the following errors has been made in the multi-
function input (H1-01 to H1-05) settings:
• Duplicate functions were selected.
• UP/DOWN Command(10 and 11) were not selected

simultaneously.

• The up/down commands (10 and 11) and Accel/

Decel Ramp Hold (A) were selected at the same
time.

• More than one of the Speed Search inputs (61, 62,

64) were set simultaneously.

• External Baseblock NO (8) and External Baseblock

NC (9) were selected at the same time.

• The up/down commands (10 and 11) were selected

while PID Control was enabled.

• The Emergency Stop Command NO (15) and NC(17)

are set simultaneously.

• PID is enabled and UP and/or DOWN (10 / 11) com-

mand are set.

• HSB (68) and KEB (65/66) command are set simulta-

neously.

Verify the parameter settings in H1-

††

OPE05

Sequence Select

RUN/Reference Command Selection Error
The Reference Source Selection b1-01 and/or the RUN
Source Selection parameter b1-02 are set to 3 (option
board) but no option board is installed.

• Verify that the board is installed. Remove the power

supply and re-install the option board again

• Recheck the setting of b1-01 and b1-02

OPE06

PG Opt Missing

Control Method Selection Error
One of the control methods needing a PG feedback
was selected (A1-02 = 1 or 3), but a PG option board is
not installed.

Verify the control method selection in parameter A1-02
and/or the installation of the PG option board.

Display

Alarm

Fault

Meaning

Corrective Actions

Advertising