FC-21 Flow Computer

3.2 Corrected Liquid Volume

Measurements:
A flowmeter measures the actual volume in a liquid line. A temperature
sensor is installed to correct for liquid thermal expansion.

Calculations:
• Corrected Volume is calculated using the flow and temperature inputs

as well as the thermal expansion coefficient stored in the flow computer.
Use the "SET FLUID PROPERTIES" submenu to define reference
temperature and density values for standard conditions.

Output Results:
• Display Results

Flow Rate, Resettable Total, Non-Resettable Total, Temperature,
Density

• Analog Output

Rate, Total, Temperature or Density

• Pulse Output

Total

• Relay Outputs

Rate , Total or Temperature Alarms

Applications:
Monitoring corrected volume flow and total of any liquid. Flow alarms are
provided via relays and datalogging is available via analog (4-20mA) and
serial outputs.

Corrected
Liquid Volume

Volume Flow

As calculated in section 3.1

Corrected Volume Flow

(Temp. Transmitter)

Corrected Volume Flow = vol. flow * (1 - Therm.Exp.Coef. *(Tf-Tref))

2

Calculations

Corrected
Liquid Volume
Illustration