Quadra-Fire • QV36DC-A • 2161-900 Rev. C • 6/09

23

5. Install Firestops

For Horizontal Runs - Firestops are REQUIRED on
both sides of a combustible wall through which the vent
passes.

NOTE: Model DVP-TRAP does not need an exterior
fi restop on an exterior combustible wall.

To install fi restops for horizontal runs that pass through
either interior or exterior walls:

• Cut a 10-inch by 12-inch (254mm X 305mm) hole through

the wall.

NOTE: The center of the hole is one (1) inch (25.4mm)
above the center of the horizontal vent pipe.

• Position

the

fi restops on both sides of the hole previously

cut and secure the fi restops with nails or screws.

• The heat shields of the fi restops MUST BE placed to-

wards the top of the hole.

• Continue the vent run through the fi restops.

Figure 24. Heat Shield, Interior & Exterior Firestops

TRIM HEAT
SHIELD IF TOO
LONG, ADD TO
SHIELD IF TOO
SHORT

EXTERIOR
FIRESTOP

INTERIOR

FIRESTOP

HEAT SHIELD

NOTE: There must be NO INSULATION or other
combustibles inside the framed fi restop opening.

Figure 23. 10” x 12” Hole and Vent Pipe

10 in.

12 in.

INTERIOR

WALL SHIELD