Instructions mcs mcr master control set / reset – Toshiba 6F3B0253 User Manual

Page 135

Advertising
background image

6F3B0253

Basic Hardware and Function

133

7. Instructions

MCS
MCR

Master control set / reset

Expression

Input

[ MCS ]

[ MCR ]

Function

When the MCS input is ON, ordinary operation is performed. When the MCS input is OFF, the state
of left power rail between MCS and MCR is turned OFF.

Execution condition

MCS
input

Operation

Output

OFF

Sets OFF the left power rail until MCR

ON

Ordinary operation

Operand

No operand is required.

Example

When X000 is OFF, Y021 and Y022 are turned OFF regardless of the states of X001 and
X002.

Equivalent circuit

X000

X001

Y021

X002

Y022

Note

MCS and MCR must be used as a pair.

Nesting

is

not

allowed.