1. System Configuration

1.4 I/O expansion

The T1-16S provides I/O expandability by connecting the I/O modules. Up to eight
I/O modules can be connected.

Available I/O modules

DI116M:

16 points DC input

DO116M:

16 points DC output

DD116M:

8 points DC input + 8 points DC output

RO108M:

8 points relay output

AD121M:

1 channel analog input (0 to 5V or 0 to 20mA)

AD131M:

1 channel analog input (-10 to +10V)

DA121M:

1 channel analog output (0 to 20mA)

DA131M:

1 channel analog output (-10 to +10V)

TC111M:

1 channel thermocouple input (type K, J, E, or

±

50mV)

FR112M:

TOSLINE-F10 remote station

T1-16S maximum configuration

(1) The 5Vdc power to the I/O modules is supplied from the main unit. The main

unit can supply maximum 1.5A of the 5Vdc power to the I/O modules. Check
the current consumption of each I/O module used. Refer to section 2.1.

(2) The connecting order of the I/O modules is not restricted except TOSLINE-

F10 remote station FR112M. When the FR112M is used, it must be the right
end module.

(3) If more than 8 I/O modules are connected, the T1-16S cannot operate

normally.

T1-16S
main unit

Up to 8 I/O modules

NOTE