4. Installation and Wiring

4.3 Wiring terminals

The terminal screw size of the T1-16S is M3. Use crimp-style terminals of 7mm width
or less useable for M3. The terminal block is not removable (fixed).

For input and output signal connections, refer to sections 2.4 and 3.

T1-MDR16SS .... AC power supply model

T1-MDR16SSD.. DC power supply model

3

1

0

L

4

2

NC

N

MDR16SS

DC OUT

+

24

22

20

6

23

21

Vin

7

5

26

27

25

C

C

C

RELAY OUT

DC IN

RS-485 (Enhanced model only)

3

1

0

+

4

2

NC

-

MDR16SSD

DC OUT

NC

NC

24

22

20

6

23

21

Vin

7

5

26

27

25

C

C

C

RELAY OUT

DC IN

RS-485 (Enhanced model only)

TXA RXA RXB

TXB TRM SG

TXA RXA RXB

TXB TRM SG

(1) NC stands for ”no connect”. Do not use the NC terminals for wire

relaying or branching.

(2) For the connections of the RS-485 communication port (the upper

terminal block), refer to the separate manual “T1-16S User’s Manual -
Communication Function -.

The applicable wire size is 0.3mm

2

(22 AWG) to 1.25mm

2

(16 AWG). The table below

shows the recommended wire size.

Type of signal

Recommended wire size

Power

1.25mm

2

(16 AWG)

Grounding

1.25mm

2

(16 AWG)

I/O signals

0.3mm

2

(22 AWG) to 0.75mm

2

(18 AWG)

!

CAUTION

1. Turn off power before wiring to minimize the risk of electrical shock.

2. Exposed conductive parts of wire can cause electrical shock. Use

crimp-style terminals with insulating sheath or insulating tape to cover
the conductive parts. Also close the terminal covers securely on the
terminal blocks when wiring has been completed.

3. Turn off power before removing or replacing units, modules, terminal

blocks or wires. Failure to do so can cause electrical shock or damage
to the T1-16S and related equipment.

NOTE

NOTE