Installation and wiring – Toshiba 6F3B0253 User Manual

Page 61

Advertising
background image

6F3B0253

Basic Hardware and Function

59

4. Installation and Wiring

4.5 Power supply wiring

Wire the power source to the T1-16S power supply terminals.

Insulation
transformer

Line filter

Power source

T1-16S

Power

conditions:

AC power supply type

DC power supply type

Rated voltage

100 to 240Vac, +10/-15%

24Vdc, +20/-15%

Frequency

50/60Hz,

±

5%

-

Power consumption

45VA or less

18W or less

Retentive power
interruption

Continuous operation for less than 10ms

1.25mm

2

(16 AWG) twisted-pair cable should be used for the power cable.

The power cable should be separated from other cables.

!

CAUTION

1. Turn off power before wiring to minimize the risk of electrical shock.

2. Applying excess power voltage to the T1-16S can cause explosion or

fire. Apply power of the specified ratings described below.

Advertising