Toshiba ICC Multiprotocol Ethernet Interface ASD-G9ETH User Manual

Page 63

Advertising
background image

62

ICC

Point-to-point class 1 connected messages will be produced targeting the
IP address of the device that instantiated the connection, port 0x08AE (port
2222).

If a class 1 connection’s consuming half (O

→T) times out, then the

producing half (T

→O) will also time-out and will stop producing.

If a class 1 or class 3 connection timeout occurs, the driver will trigger a
timeout event as described in section 10.7.4.


13.2.2 ControlLogix Examples: Setup

This section will demonstrate how to initially setup a ControlLogix PLC (such as
a 1756-L61) coupled with a 1756-ENBT communications bridge (adjust this
procedure according to your specific equipment). Later sections will provide
specific read/write examples using this configuration with I/O or explicit
messaging.

1) Run RSLogix 5000, and create a new configuration.

2) To add a 1756-ENET/B to your I/O configuration, first switch to offline

mode.

3) Right click on the I/O Configuration node in the controller organizer view

and choose “New Module…”

4) The “Select Module” window will open.

5) Under “Communications”, select “1756-ENET/B”, and click OK. Refer to

Figure 58.

Figure 58: Adding a New Module