ICC

default 30000000 (30s in 1uS increments) to 1000000 (1s). This value
determines how long to wait before timing out and retransmitting a
connection request if a connection failure occurs. Refer to Figure 68.

Figure 68: Reduce the UnconnecteTimeout Value

f)

Collapse the “connection” tag again by clicking on the “-“ sign next to
the tag name.

g) Select the “Edit Tags” tab again. Create another new tag by entering

“data_array” in the next blank Name field, and change its Data Type
by typing in “INT[100]” in the Data Type field. This tag is an array of
INTs that will be able to hold up to 100 16-bit registers from the drive.
Always make sure that the destination tag size is large enough to hold
all elements to be read.


2) Add a MSG instruction to the main program.

a) Double click “MainRoutine” under Tasks …MainTask …MainProgram

in the controller organizer view.

b) Right click on the first ladder logic rung in the MainRoutine window

and select “Add Ladder Element...”

c) The “Add Ladder Element” window appears.

d) Select the “MSG” instruction in the Input/Output folder. Refer to

Figure 69.

e) Click

OK.

Figure 69: Adding a MSG Instruction