ICC

Figure 73: Selecting the Destination Element

d) “Communication” tab settings (refer to Figure 74):

i)

Enter the Path to the interface card. A typical path is formatted as
Local_ENB,2,target_IP_address”, where:

Local_ENB is the name of the 1756-ENBx module in the local
chassis (we named ours “EIP” in section 13.2.2),

2 is the Ethernet port of the 1756-ENBx module in the local
chassis, and

target_IP_address is the IP address of the target node.

In our example, this path would be entered as
“EIP,2,192.168.16.128”.

Figure 74: Setting the Communication Path