2. outdoor unit, Rav-sp180at2-ul – Toshiba CARRIER RAV-SP300AT2-UL User Manual

Page 16

Advertising
background image

– 16 –

3-2. Outdoor Unit

RAV-SP180AT2-UL

Standard

Cooling Overload

Low load

Standard

Heating Overload

Low load

Pressure

(psi)

(MPa)

Pd

Ps

Pd

Ps

416.2 145.0 2.87

1.00

517.7 159.5 3.57

1.10

248.0 110.2 1.71

0.76

327.7 98.6 2.26

0.68

471.3 165.3 3.25

1.14

290.0 36.3 2.00

0.25

Pipe surface temperature °F (°C)

Discharge

Suction

Indoor heat Outdoor heat

exchanger

exchanger

(TD)

(TS)

(TC)

(TE)

161.6

60.8

55.4

107.6

(72)

(16)

(13)

(42)

190.4

68

66.2

125.6

(88)

(20)

(19)

(52)

113.0

53.6

44.6

55.4

(45)

(12)

( 7)

(13)

150.8

42.8

98.6

37.4

(66)

( 6)

(37)

( 3)

172.4

68.0

127.4

60.8

(78)

(20)

(53)

(16)

172.4

–0.4

93.2

–0.4

(78)

(–18)

(34)

(–18)

Compressor

drive revolution

frequency

(rps)

58

65

30

64

30

88

Indoor

fan

HIGH

HIGH

LOW

HIGH

LOW

HIGH

Indoor/Outdoor

temp. conditions

(DB/WB) °F °C)

Indoor

Outdoor

80.6/66.2

95/–

(27/19)

(35/–)

89.6/75.2

109.4/–

(32/24)

(43/–)

64.4/59.9

23/–

(18/15.5)

(–5/–)

68/–

44.6/42.8

(20/–)

(7/6)

86/–

75.2/64.4

(30/–)

(24/18)

59/–

5/–

(15/–)

(–15/–)

TE sensor

TO sensor

TS

sensor

TD

sensor

Heat exchanger

Ø8 ripple, 2 rows, 20 stages

FP1.3, flat fin

Accumulator

(1L)

Rotary compressor

(DA150A1F-21F)

Strainer

Refrigerant pipe
at liquid side Ø6.4
Packed valve

Refrigerant pipe
at gas side Ø12.7
Packed valve

Distributor

In cooling operation
In heating operation

4-way valve

(STF-0213Z)

2-step muffler

Ш25 Ч 200L

Muffler

Ш31.75 Ч 200L

Muffler

Ш19.05 Ч 160L

PMV

(Pulse Motor Valve)

(CAM-B30YGTF-2)

Advertising