Setup at local site and others, 1. outdoor unit – Toshiba CARRIER RAV-SP300AT2-UL User Manual

Page 74

Advertising
background image

– 74 –

10. SETUP AT LOCAL SITE AND OTHERS

10-1. Outdoor Unit

10-1-1. Various Setting on Outdoor Unit (Power save, Cooling-only, etc.)

The following settings are available by DIP switch setup and jumper line setup.

<RAV-SP180AT2-UL>

Power saving setting

Cooling only setting

SW802

3

2

1

ON

Function

Power save

setup

Cooling-only

setup

Set position

Control contents

When using the power saving function, turn on switches.
The control to lower the compressor frequency (approx. -10%) is

performed by indoor heat exchanger temp. in heating operation.

When using the outdoor unit as a cooling-only machine, turn on

switches. (“OF” of DN cord on the remote controller also can be

used for changing the machine to the cooling-only model.)

<RAV-SP240, SP300, SP360, SP420AT2-UL>

Function

High static

pressure

setup

Power save

setup

Snow-proof

fan control

Defrost

time change

Max.

frequency

change

Cooling-only

setup

Set position

J805, J806

J807

J808

Control contents

Turn the switch to ON when mounting a duct to the discharge port

of the outdoor unit.
Add 3 taps to the upper limit value of the outdoor fan tap.
The operation is performed with

(Max: Upper fan: 890 rpm / Lower fan: 910 rpm (WF)).
In this case, the upper limit value of static pressure for duct is 5Pa

or less on 77°F (25°C) degrees and please use straight duct.
In this case, the outdoor noise level may increase.

Turn the switch to ON when using the power save function.
The control to lower the compressor frequency (Approx. –10%) is

performed by indoor heat exchanger temp. in heating operation.

When snow enters from clearance of the fan guard or heat

exchanger into blast path and it is accumulated, the control to

prevent generation of motor lock is validated.
When outside temp. is below 32°F (0°C) though the compressor

stops, the outdoor fan operates with W5.

The defrost interval is cut to shorten it than the standard status.
For contents of control and cutting method, refer to

10. Defrost control (See to Page 43).

When it is needed to lower the maximum value of the compressor

frequency, cut the jumper line. Max. frequency at cooling/heating is

lowered.
In this case the Max. capacity decreases.

Max. frequency of compressor

When using the air conditioner as a cooling-only conditioner, cut

the jumper line. (An air conditioner can be changed to cooling-only

conditioner by “0F” of DN code on the remote controller.)

4

3

2

1

ON

High static pressure setup

Power save setup

Snow-proof fan control

SW802

all are OFF at shipment.

RAV-

Model

Standard status

When J807 is cut

SP240

COOL

HEAT

72.0

99.6

72.0

79.2

SP300

COOL

HEAT

53.4

71.4

53.4

64.2

SP360, SP420

COOL

HEAT

64.2

90.6

64.2

72.0