– 28 –

Gauge manifold

[ Cylinder with siphon ]

[ Cylinder without siphon ]

OUTDOOR unit

Gauge manifold

OUTDOOR unit

Refrigerant

cylinder

Electronic

balance

Refriger

ant

cylinder

Electronic

balance

Siphon

R410A refrigerant is HFC mixed refrigerant.
Therefore, if it is charged with gas, the composition

of the charged refrigerant changes and the

characteristics of the equipment varies.

Fig. 6-4-2

6-5. Brazing of Pipes

6-5-1. Materials for Brazing

1. Silver brazing filler

Silver brazing filler is an alloy mainly composed

of silver and copper.
It is used to join iron, copper or copper alloy, and

is relatively expensive though it excels in

solderability.

2. Phosphor bronze brazing filler

Phosphor bronze brazing filler is generally used

to join copper or copper alloy.

3. Low temperature brazing filler

Low temperature brazing filler is generally called

solder, and is an alloy of tin and lead.
Since it is weak in adhesive strength, do not use

it for refrigerant pipes.

1) Phosphor bronze brazing filler tends to react with

sulfur and produce a fragile compound water

solution, which may cause a gas leakage.

Therefore, use any other type of brazing filler at

a hot spring resort, etc., and coat the surface

with a paint.

2) When performing brazing again at time of

servicing, use the same type of brazing filler.

6-5-2. Flux

1. Reason why flux is necessary

• By removing the oxide film and any foreign

matter on the metal surface, it assists the flow

of brazing filler.

• In the brazing process, it prevents the metal

surface from being oxidized.

• By reducing the brazing filler's surface tension,

the brazing filler adheres better to the treated

metal.

1) Be sure to make setting so that liquid can be charged.
2) When using a cylinder equipped with a siphon, liquid can be charged without turning it upside down.

It is necessary for charging refrigerant under condition of liquid because R410A is mixed type of refrigerant.
Accordingly, when charging refrigerant from the refrigerant cylinder to the equipment, charge it turning the

cylinder upside down if cylinder is not equipped with siphon.