3. Outdoor fan control

Revolution frequency allocation of fan taps [rpm]

3-1) Cooling fan control



The outdoor fan is controlled by TE sensor, TO sensor and the operation frequency. It is controlled

by every 1 tap of DC fan control (15 taps).

‚

Only for 60 seconds after start-up of operation, it is fixed by the maximum fan tap corresponded to

the zone in the following table, and then the fan is controlled by temperature of TE sensor.

ƒ

When temperature of TD sensor became high sufficiently, it is controlled so that the fan revolution

frequency will become higher ignoring TE sensor temperature.

+1 tap / 20 sec

Up to the maximum

revolution frequency of each zone

Operation with W1 in case of fan-OFF

Revolution frequency hold

Operation with
the maximum tap
of each zone

Operation with WF

Normal fan control
by TE sensor

–1 tap / 20 sec

Down to the minimum

revolution frequency of each zone

TE

˚F (˚C)

TD

˚F (˚C)

185 (85)

176 (80)

167 (75)

149 (65)

89.6 (32)

84.2 (29)

RAV-SP

180AT2-UL

W1

W2

W3

W4

W5

W6

W7

W8

W9

WA

WB

WC

WD

WE

WF

200

250

300

400

480

500

520

560

640

670

700

750

800

880

980

Temp. range

100.4°F (38°C) ≤ TO

82.4°F (28°C) ≤ TO < 100.4°F (38°C)

59°F (15°C) ≤ TO < 82.4°F (28°C)

41.9°F (5.5°C) ≤ TO < 59°F (15°C)

32°F (0°C) ≤ TO < 41.9°F (5.5°C)

23°F (–5°C) ≤ TO < 32°F (0°C)

TO < 23°F (–5°C)

TO error

20 Hz or lower

20Hz to 45Hz

45Hz or higher

Min.

Max.

Min.

Max.

Min.

Max.

W6

WB

W7

WE

W9

WF

W5

WA

W6

WD

W8

WE

W3

W7

W4

W9

W6

WB

W2

W5

W3

W7

W5

W9

W1

W3

W2

W5

W3

W7

W1

W2

W1

W3

W2

W4

OFF

OFF

OFF

OFF

W1

W3

W1

WB

W1

WE

W1

WF