General data, 12½ ton) general data – Trane PKGP-PRC001-EN User Manual

Page 12

Advertising
background image

12

PKGP-PRC001-EN

(12½ Ton)

General
Data

*Indicates both downflow and horizontal units.

Table GD-1 — General Data

12½ Ton Downflow and Horizontal Units

WCD150B3, B4, BW

WCH150B3, B4, BW

Cooling Performance

1

Gross Cooling Capacity

152,00

152,000

EER

2

9.5

9.5

Nominal CFM / ARI Rated CFM

4,400 / 4,400

4,400 / 4,400

ARI Net Cooling Capacity

144,000

144,000

Integrated Part Load Value

3

9.9

9.9

System Power KW

15.16

15.16

Heating Performance

1

High Temp. Btuh Rating

135,000

132,000

System Power KW/COP

12.76/3.10

12.48/3.10

Low Temp. Btuh Rating

78,000

72,000

System Power KW/COP

10.88/2.1

10.55/2.0

HSPF (Btu/Watts-hr)

Compressor
No./Type

2/Scroll

2/Scroll

ARI Sound Rating (BELS)

4

9.2

9.2

Outdoor Coil — Type

Hi-Performance

Hi-Performance

Tube Size (in.) OD

.375

.375

Face Area (sq ft)

23.96

23.96

Rows/FPI

2/16

2/16

Refrigerant Control

Expansion Valve

Expansion Valve

Indoor Coil — Type

Hi-Performance

Hi-Performance

Tube Size (in.)

.375

.375

Face Area (sq ft)

15.83

17.50

Rows/FPI

2/15

2/15

Refrigerant Control

Capillary Tube

Capillary Tube

Drain Connection No./Size (in.)

1/1.00 NPT

1/1.00 NPT

Outdoor Fan — Type

Propeller

Propeller

No. Used/Diameter (in.)

2/26

2/26

Drive Type/No. Speeds

Direct/1

Direct/1

CFM

10,800

10,800

No. Motors/HP

2/.50

2/.50

Motor RPM

1,110

1,110

Indoor Fan — Type

FC Centrifugal

FC Centrifugal

No. Used

1

1

Diameter x Width (in.)

15 x 15

15 x 15

Drive Type/No. Speeds

Belt/1

Belt/1

No. Motors

1

1

Motor HP (Standard/Oversized)

3.0/5.0

3.0/5.0

Motor RPM (Standard/Oversized)

1,740/3,450

1,740/3,450

Motor Frame Size (Standard/Oversized)

145T/145T

145T/145T

Filters — Type Furnished

6

Throwaway

Throwaway

(No.) Size Recommended (in.)

(2) 20 x 20 x 2

(2) 20 x 20 x 2

(4) 20 x 25 x 2

(4) 20 x 25 x 2

Refrigerant Charge (Lbs of R-22)

5

11.1/11.4 Circuit

11.5/11.8 Circuit

Notes:
1. Cooling Performance and Heating Performance is rated at 95°F ambient, 80°F entering dry bulb, 67°F entering wet bulb. Gross capacity does not include the effect of fan motor heat.

ARI capacity is net and includes the effect of fan motor heat. Units are suitable for operation to ±20% of nominal cfm. Certified in accordance with the Unitary Large Equipment
certification program, which is based on ARI Standard 340/360-93.

2. EER is rated at ARI conditions and in accordance with ASHRAE test procedures.
3. Integrated Part Load Value is based in accordance with ARI Standard 210/240 or 340. Units are rated at 80°F entering dry bulb, and 67°F entering wet bulb at ARI rated cfm.
4. Sound Rating shown is tested in accordance with ARI Standard 270 or 370.
5. Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.
6. Optional 2 inch pleated filter also available.