Electrical data – Trane PKGP-PRC001-EN User Manual

Page 32

Advertising
background image

32

PKGP-PRC001-EN

Electrical
Data

*

Indicates both downflow and horizontal units.

Table ED-5 — Electrical Characteristics — Compressor Motor And Condenser Motor — 60 Cycle

Unit

Tons

Model No.

No.

Volts

Phase

HP

2

RPM

RLA

LRA

No. Phase

HP

FLA

LRA

WC

*

150B3

2

208-230

3

6.00

3450

21.7

156

2

1

.50

3.2

8.8

12½

WC

*

150B4

2

460

3

6.00

3450

10.0

75

2

1

.50

1.6

4.0

WC

*

150BW

2

575

3

6.00

3450

8.2

54

2

1

.50

1.3

3.2

WC

*

180B3

2

208-230

3

5.70/9.00

3450/3500

30.1/20.4

225/156

2

1

.50

3.2

8.8

15

WC

*

180B4

2

460

3

5.70/9.00

3450/3500

15.6/10.8

114/75

2

1

.50

1.6

4.0

WC

*

180BW

2

575

3

5.70/9.00

3450/3500

12.1/8.5

80/54

2

1

.50

1.3

3.2

WC

*

240B3

2

208-230

3

9.00

3500

30.1

225

2

1

1.00

5.5

18.3

20

WC

*

240B4

2

460

3

9.00

3500

15.8

114

2

1

1.00

2.9

9.3

WC

*

240BW

2

575

3

9.00

3500

12.2

80

2

1

1.00

2.0

5.7

Notes:
1

Amp draw for each motor; multiply value by numbers of motors to determine total amps.

2. HP for each compressor.

Amps

1

Amps

1

Condenser Fan Motors

Compressor Motors

Advertising